Investigation into the Degradation Process in Transformer Boards’


UĞUR M., EMİN Z.

Yıldız Teknik Üniversitesi Dergisi, vol.3-4, pp.83-90, 1997 (Peer-Reviewed Journal)

  • Publication Type: Article / Article
  • Volume: 3-4
  • Publication Date: 1997
  • Journal Name: Yıldız Teknik Üniversitesi Dergisi
  • Journal Indexes: TR DİZİN (ULAKBİM)
  • Page Numbers: pp.83-90
  • Istanbul University Affiliated: No

Abstract

 

            Some transformer boards taken out of service have shown unexpected discharge damages. Bubbles on the surface have been shown to be markers for discharge damages beneath the surface. Since the transformer design stresses have been way below those which would allow discharges within the oil it is apparent that unforeseen mechanisms are present in the operational transformers. An investigation has been undertaken to try and reproduce these damages on a short time scale in the laboratory. Dry and oil impregnated transformer boards were tested under AC high voltage with different electrode configurations in various conditions. The effect of moisture content on the breakdown strength is also investigated. The paper reports and compares the factors associated with the aging and degradation of the transformer boards.

Yapılan incelemeler sonucunda servis dışı bırakılan trafoların bazılarının karton mukavvalarında beklenmedik aşınmalar meydana geldiği gözlenmiştir. Yüzeydeki boşalmaların, yüzey altındaki elektriksel boşalmalardan kaynaklandığı düşünülmektedir. Araştırmanın amacı meydana gelen bu aşınımı kısa zamanda laboratuar koşullarında elde etmek ve bu olaya sebebiyet veren faktörleri belirlemektir. Bu amaçla kuru ve yağ emdirilmiş mukavvalar AC gerilim altında çeşitli elektrodlar kullanılarak test edilmiş, nem miktarının delinme direncine etkisi araştırılmıştır.